QUINT-PS-100-240AC/48DC/10
Function
U OUT
[V]
U N
Output characteristic curve
At ambient temperatures T amb < +40°C, the device can con-
tinuously provide current I BOOST at nominal voltage.
In the event of a higher load, the operating point follows the
U/I characteristic curve depicted in the figure. In the event of
a short circuit or overload, the output current is limited to
< 60 °C
< 40 °C
I BOOST . Thereby, the device does not switch off, but rather
supplies a continuous output current. The secondary voltage
is reduced until the short circuit on the secondary side has
been remedied.
The U/I characteristic curve ensures that the heavily capaci-
tive loads and the consumers with DC/DC converters in the
input circuit can be fed without problems using QUINT PO-
I N
I BOOST
I OUT
[A]
WER.
Downstream fuses are triggered reliably. Selectivity in the
design of your system is guaranteed at all times.
U N = 48 V
I N = 10 A
I BOOST = 13 A
P N = 480 W
P BOOST = 625 W
Thermal behavior
With an ambient temperature of up to +40°C, the device sup-
I BOOST
I N
plies the continuous output current of I BOOST . The device can
supply a nominal output current of I N with ambient tempera-
tures of up to +60°C. In the case of ambient temperatures
above +60°C, the output current must be reduced by 2.5%
per Kelvin increase in temperature. The device does not
102549_00_en
0
0
20 40 60
Ambient temperature [°C]
switch off at ambient temperatures of +70°C or thermal over-
load. The output capacity is reduced as far as necessary to
provide device protection. After it has cooled down, the out-
put capacity is increased again.
13
PHOENIX CONTACT